BACnet is often used as an integration protocol to link multiple technologies such as HVAC, access security, fire systems and lighting control within a building.

Developed in 1987 under the guidance of the American Society of Heating Refrigerating and Airconditioning Engineers (ASHRAE), BACnet has been an ANSI standard since 1995 and an ISO standard since 2003.

In 1999, BACnet over IP was introduced as a part of Addendum A, now allowing the protocol to leverage IP network infrastructure in a building to pass BACnet communications.

In a zencontrol base DALI installation, BACnet over IP (No support for BACnet over MS/TP) is available as an integration method, allowing for BACnet communications to read the status as well as control lighting directly from a BACnet capable headend system.

For more information about the capabilities of BACnet with zencontrol, please see the following article.

On occasion, troubleshooting of a BACnet over IP installation may be necessary, the following information may assist in identifying potential issues:

1. Network Configuration

Check IP Addressing

  • Ensure devices have unique IP addresses within the same subnet or appropriately configured routing for different subnets.

  • Verify the correct Subnet Mask and Gateway settings.

Port Settings

  • Confirm all devices are using the same BACnet/IP port (default: 47808 or BAC0 in hex).

  • Check for port conflicts with other services.

Firewall/Router Rules

  • Ensure firewalls or routers allow UDP traffic on the BACnet/IP port.

  • Verify that features like port filtering, NAT, or VLANs are not restricting BACnet traffic.

Broadcasting

  • Confirm the network supports broadcast traffic (e.g., Who-Is and I-Am messages).

  • Use BBMD (BACnet/IP Broadcast Management Device) to enable communication across subnets if broadcasts are restricted.


2. BACnet Configuration

Device Instance

  • Ensure each device has a unique Device Instance to avoid conflicts.

BACnet Object Configuration

  • Verify that required BACnet objects (e.g., Analog Input, Binary Output) are correctly configured.

  • Use BACnet tools to confirm object accessibility.

Network Numbers

  • Assign unique BACnet Network Numbers for each network segment.

Device Communication

  • Test Who-Is/I-Am messages to confirm device visibility.

  • Check the functionality of Read Property and Write Property services.


3. Network Traffic

Packet Sniffing

  • Use tools like Wireshark to monitor BACnet traffic.

    • Look for Who-Is/I-Am, Read Property, or Write Property packets.

    • Identify issues such as Malformed Packets or No Responses.

Network Congestion

  • Monitor for excessive broadcast traffic that can overload the network.

  • Use unicast messages or adjust BBMD configurations to limit broadcast traffic.

Latency

  • Measure network latency to ensure it is within acceptable limits for BACnet communication.


4. Physical Network

Cabling

  • Inspect Ethernet cables and connectors for damage or improper termination.

  • Test basic connectivity with tools like ping.

Switches and Hubs

  • Verify that network switches can handle the traffic load.

  • Avoid network loops, which can cause broadcast storms.

Power Issues

  • Ensure devices receive adequate power, particularly if using PoE (Power over Ethernet).


5. Testing Tools

  • Utilize BACnet diagnostic tools such as:

    • YABE (Yet Another BACnet Explorer) - Highly recommended! (And free)

    • BACnet/IP network analyzers

    • Wireshark with BACnet protocol dissectors

While some of the above advice is general in nature, it is best to understand that as BACnet allows communications between devices beyond a zencontrol installation, general troubleshooting knowledge will assist in correcting any potential installation issues.

Tools such as YABE can also quickly narrow down installation faults by demonstrating functionality of individual devices. This allows you to identify who may be responsible for a potential issue on site.